Sign In | Join Free | My uabig.com |
|
Brand Name : SIEMENS
Model Number : 6ES7510-1DJ01-0AB0
Certification : CE
Place of Origin : Germany
MOQ : 1
Price : USD
Payment Terms : L/C, T/T
Supply Ability : 100
Delivery Time : 10-12Days
Packaging Details : 15,10 x 15,40 x 4,60
SIEMENS 6ES7510-1DJ01-0AB0 SIMATIC MEMORY CARD REQUIRED, BUSADAPTER REQUIRED FOR PORT 1 AND
The SIEMENS 6ES7510-1DJ01-0AB0 is a central processing unit (CPU) that is part of the SIMATIC S7-1500 automation system. Here are the key details about this CPU:
SIMATIC Memory Card Required:
- Like other SIMATIC S7-1500 CPUs, this model requires a SIMATIC memory card to be inserted for operation.
- The memory card provides storage for the user program, configuration data, and other runtime information.
Busadapter Required for Port 1 and Port 2:
- This CPU has two Ethernet/PROFINET ports.
- However, to use these ports, a separate busadapter is required to be connected.
- The busadapter provides the necessary connectivity for the Ethernet/PROFINET interfaces.
Other Features:
- CPU Type: CPU 1510SP-1 PN
- Work Memory: 150 KB for program and 1 MB for data
- Compact, space-saving design in an ET 200SP module
- Part of the modular SIMATIC S7-1500 system
- Programmed using the STEP 7 engineering software
The key distinguishing features of this CPU model are its compact, space-saving design in the ET 200SP module format and the requirement for a busadapter to be connected to the Ethernet/PROFINET ports.
This makes the CPU 1510SP-1 PN well-suited for applications where space is limited, such as in distributed control systems or in confined areas. The busadapter requirement provides flexibility in terms of the type of network connectivity required for the application.
Overall, this CPU model is a compact and versatile option within the SIMATIC S7-1500 automation system, designed for applications that need a smaller form factor but still require the capabilities of the S7-1500 platform.
General information | ||
Product type designation | CPU 1510SP-1 PN | |
HW functional status | FS05 | |
Firmware version | V2.9 | |
Product function | ||
● I&M data | Yes; I&M0 to I&M3 | |
● Module swapping during operation (hot swapping) | Yes; Multi-hot swapping | |
● Isochronous mode | Yes; Only with PROFINET; with minimum OB 6x cycle of 625 µs | |
Engineering with | ||
● STEP 7 TIA Portal configurable/integrated from version | V17 (FW V2.9) / V13 SP1 Update 4 (FW V1.8) or higher | |
Configuration control | ||
via dataset | Yes | |
Control elements | ||
Mode selector switch | 1 | |
Supply voltage | ||
Rated value (DC) | 24 V | |
permissible range, lower limit (DC) | 19.2 V | |
permissible range, upper limit (DC) | 28.8 V | |
Reverse polarity protection | Yes | |
Mains buffering | ||
● Mains/voltage failure stored energy time | 5 ms | |
Input current | ||
Current consumption (rated value) | 0.6 A | |
Current consumption, max. | 0.9 A | |
Inrush current, max. | 4.7 A; Rated value | |
I²t | 0.14 A²·s | |
Power | ||
Infeed power to the backplane bus | 8.75 W | |
Power loss | ||
Power loss, typ. | 5.6 W | |
Memory | ||
Number of slots for SIMATIC memory card | 1 | |
SIMATIC memory card required | Yes | |
Work memory | ||
● integrated (for program) | 100 kbyte | |
● integrated (for data) | 750 kbyte | |
Load memory | ||
● Plug-in (SIMATIC Memory Card), max. | 32 Gbyte | |
Backup | ||
● maintenance-free | Yes | |
CPU processing times | ||
for bit operations, typ. | 72 ns | |
for word operations, typ. | 86 ns | |
for fixed point arithmetic, typ. | 115 ns | |
for floating point arithmetic, typ. | 461 ns | |
CPU-blocks | ||
Number of elements (total) | 4 000; Blocks (OB, FB, FC, DB) and UDTs | |
DB | ||
● Number range | 1 ... 60 999; subdivided into: number range that can be used by the user: 1 ... 59 999, and number range of DBs created via SFC 86: 60 000 ... 60 999 | |
● Size, max. | 750 kbyte; For DBs with absolute addressing, the max. size is 64 KB | |
FB | ||
● Number range | 0 ... 65 535 | |
● Size, max. | 100 kbyte | |
FC | ||
● Number range | 0 ... 65 535 | |
● Size, max. | 100 kbyte | |
OB | ||
● Size, max. | 100 kbyte | |
● Number of free cycle OBs | 100 | |
● Number of time alarm OBs | 20 | |
● Number of delay alarm OBs | 20 | |
● Number of cyclic interrupt OBs | 20; With minimum OB 3x cycle of 500 µs | |
● Number of process alarm OBs | 50 | |
● Number of DPV1 alarm OBs | 3 | |
● Number of isochronous mode OBs | 1 | |
● Number of technology synchronous alarm OBs | 2 | |
● Number of startup OBs | 100 | |
● Number of asynchronous error OBs | 4 | |
● Number of synchronous error OBs | 2 | |
● Number of diagnostic alarm OBs | 1 | |
Nesting depth | ||
● per priority class | 24 | |
Counters, timers and their retentivity | ||
S7 counter | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
IEC counter | ||
● Number | Any (only limited by the main memory) | |
Retentivity | ||
— adjustable | Yes | |
S7 times | ||
● Number | 2 048 | |
Retentivity | ||
— adjustable | Yes | |
IEC timer | ||
● Number | Any (only limited by the main memory) | |
Retentivity | ||
— adjustable | Yes | |
Data areas and their retentivity | ||
Retentive data area (incl. timers, counters, flags), max. | 128 kbyte; Available retentive memory for bit memories, timers, counters, DBs, and technology data (axes): 88 KB | |
Flag | ||
● Size, max. | 16 kbyte | |
● Number of clock memories | 8; 8 clock memory bit, grouped into one clock memory byte | |
Data blocks | ||
● Retentivity adjustable | Yes | |
● Retentivity preset | No | |
Local data | ||
● per priority class, max. | 64 kbyte; max. 16 KB per block | |
Address area | ||
Number of IO modules | 1 024; max. number of modules / submodules | |
I/O address area | ||
● Inputs | 32 kbyte; All inputs are in the process image | |
● Outputs | 32 kbyte; All outputs are in the process image | |
per integrated IO subsystem | ||
— Inputs (volume) | 8 kbyte | |
— Outputs (volume) | 8 kbyte | |
per CM/CP | ||
— Inputs (volume) | 8 kbyte | |
— Outputs (volume) | 8 kbyte | |
Subprocess images | ||
● Number of subprocess images, max. | 32 | |
Address space per module | ||
● Address space per module, max. | 288 byte; For input and output data respectively | |
Address space per station | ||
● Address space per station, max. | 2 560 byte; for central inputs and outputs; depending on configuration; 2 048 bytes for ET 200SP modules + 512 bytes for ET 200AL modules | |
Hardware configuration | ||
Number of distributed IO systems | 32; A distributed I/O system is characterized not only by the integration of distributed I/O via PROFINET or PROFIBUS communication modules, but also by the connection of I/O via AS-i master modules or links (e.g. IE/PB-Link) | |
Number of DP masters | ||
● Via CM | 1 | |
Number of IO Controllers | ||
● integrated | 1 | |
● Via CM | 0 | |
Rack | ||
● Modules per rack, max. | 80; CPU + 64 modules + server module (mounting width max. 1 m) + 16 ET 200AL modules | |
● Quantity of operable ET 200SP modules, max. | 64 | |
● Quantity of operable ET 200AL modules, max. | 16 | |
PtP CM | ||
● Number of PtP CMs | the number of connectable PtP CMs is only limited by the number of available slots |
![]() |